EVAPORATOR ASSEMBLY MAINTENANCE - CONTINUED
EVAPORATOR ASSEMBLY MAINTENANCE - CONTINUED

Crew Protection Kit For M915A3P1, M915A2P1, M916A3P1, M917A2P1, M915A401, M917A1P1, M916A1P1, And M916A2P1 - 3 Page Navigation
  77    78    79    80    81  82  83    84    85    86    87  
img
TB 9-2320-302-13&P-3
EVAPORATOR ASSEMBLY MAINTENANCE - CONTINUED
0017 00
REMOVAL - CONTINUED
WARNING
Contact with refrigerant can cause frostbite. Keep hands and face away to prevent personal injury.
Protective face shield must always be worn when refrigerant lines are opened, even if the gauges indi-
cate the system is empty.
Always use caution if a fitting is removed. Slowly loosen the fitting. If the system is still under any
pressure, release it slowly in a well-ventilated area.
DO NOT smoke when servicing A/C or wherever refrigerant gas may be present.
Failure to follow these warnings may result in injury or death to personnel.
CAUTION
Cap all A/C hose ends and component connections during removal to protect against contamination. Failure
to comply may cause damage to equipment.
NOTE
Tag wires and hoses to aid in installation.
9.
Remove A/C hose connection (21) from evaporator assembly (1). Discard O-rings.
10.
Remove A/C hose connection (22) from evaporator assembly (1). Discard O-rings.
11.
Remove tiedown straps (20) and spiral wrap (24) from evaporator wiring harness (17) as required. Discard tiedown
straps.
12.
Disconnect RFI filter wiring harness connector (18) (red wire), connector (19) (black wire), and connector (23) (yellow
wire) from evaporator wiring harness (17).
17
18
19
20
21
22
1
449-051
24
23
0017 00-4